This post is also available in: English עברית (Hebrew)

Lightning and surge protector T1+T2+T3

Lightning protector and surge protection type T1+T2+T3 consists of varistors with a large discharge capacity combined with a gas discharge tube that ensures zero leakage current through the PE conductor.

Description

Properties:

  • Suitable for devices with considerable protection levels LPL III and LPL IV. Installed at the boundaries of LPZ 0 – LPZ 1 and above, closest to the place where an overhead line enters the building, i.e. in the main distribution boards.
  • In the case of installing type T1+T2+T3 in the main switchboard, it is also necessary to install type T2 and T3 in all additional distribution boards in the electrical installation.
  • If the product contains two PE (or PEN) terminals, it must not be used as a PE (PEN) bridge.
  • The M indicator indicates a construction type with a removable module.
  • S indicator indicates version with remote monitoring.